ANTMINER S19 Pro+ Hyd 198TH/S With ANTSPACE HK3 And DWT-T/DWT-C Dry-Wet Towers Liquid Cooling Suit

1
MOQ
15% off
Price
ANTMINER S19 Pro+ Hyd 198TH/S With ANTSPACE HK3 And DWT-T/DWT-C Dry-Wet Towers Liquid Cooling Suit
Features Gallery Product Description Request A Quote
Features
Specifications
Algorithm: SHA256
Power Consumption: 5445W
Hashrate: 198th
Coin: Bitcoin
Style: BTC Miner Liquid Cooling Suit
High Light:

Antminer S19 Pro+ Hyd Liquid Cooling Suit

,

ANTMINER S19 Pro+ Hyd 198TH/S

,

5445W BTC Miner Machine

Basic Infomation
Place of Origin: China
Brand Name: Bitmain Antminer
Certification: ce
Model Number: Antminer S19 Pro+ Hyd Liquid Cooling Suit
Payment & Shipping Terms
Delivery Time: 30 working days
Payment Terms: USDT, T/T, Bank Transfer
Supply Ability: 10PIECES/DAY
Product Description

ANTMINER S19 Pro+ Hyd 198TH/s with ANTSPACE HK3 and DWT-T/DWT-C Dry-Wet Towers Liquid Cooling Suit

 

Specification
 
Specification of ANTMINER S19 Pro+ Hyd
Product Glance Value

Version
Model No.

Crypto Algorithm

S19 Pro+ Hyd.
j0-10

SHA256

Hashrate, TH/s 198 ±3%
Power on wall @35°C, Watt(1-1) 5445 ±5%
Power efficiency on wall @35°C, J/TH(1-1) 27.5 ±5%
       
Detailed Characteristics Value
Power Supply
Power supply AC Input voltage, Volt(2-1) 342~418
Power supply AC Input Frequency Range, Hz 47~63
Power supply AC Input current, Amp(2-2) 30
Hardware Configuration
Networking connection mode RJ45 Ethernet 10/100M
Miner Size (Length*Width*Height, w/o package), mm 410*196*209
Miner Size (Length*Width*Height, with package), mm 570*316*430
Net weight, kg 15.20
Gross weight, kg 17.50
Environment Requirements
Operation temperature,°C(2-3) 0~40
Inlet water temperature,°C 20-40
Water flow L/min 8±10%
Water pressure bar ≤3.5
Storage temperature, °C -20~70
Operation humidity(non-condensing) , RH 10~90%

 

 

Specification of ANTSPACE HK3 Mining Container

Product Overview Value
Version ANTSPACE HK3
Dimensions (L*W*H) (mm) 6058*2438*2896
Miner Capacity 210 units -S19 Hyd. Series miner
Container Certification China Classification Society Certification
Safety Certification

North America/Standards:NFPA 79:2021,UL 508A:2018 R8.21,

CSA C22.2 No. 14-18,ANSI/ISO 12100:2012
EU/Standards:EN ISO 12100,EN 60204-1

Operating Power(kW) 1047~1050
PUE(Power Usage Effectiveness) 1.022(Excluding cooling tower)/1.036(Including cooling tower)
Input Voltage and Frequency 415V±5% 60Hz(North America)
400V±5% 50Hz(EU,Middle East)
Detailed Characteristics Value
Shipping Weight(T) 8
Operating Weight (T) 12
Main Switch of Power Distribution Cabinets(A) 1200(North America)
1250(EU,Middle East)
Rated Current(A) 952
Standard Power(kW) 1049
Maximum Power(kW) 1050
Rated Current per Miner(A) 10
Inlet Cable The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:
L1 single core cable 600kcMil(300mm²)x4
L2 single core cable 600kcMil(300mm²)x4
L3 single core cable 600kcMil(300mm²)x4
N Single-core cable 600kcMil(300mm²)x4
PE single-core cable 500kcMil(240mm²)x2
Connection Interface(Cooling Tower) DN125(GB/T 9119-2010 PN16 DN125)
Connection Interface(Plate Heat Exchage Interface) DN100(GB/T 9119-2010 PN16 DN100)
Flow Rate(m³/h) >85
Quantity of ANTSPACE powered by one 2500kVA Transformer 2

 

 

Specification for Dry-Wet Towers DWT-T and DWT-C

Product Overview Value
Type Dry-Wet Tower Traditional Type (DWT-T) Dry-Wet Tower Container Type (DWT-C)
Dimensions(L*W*H)(mm) 5800*2240*4200 6058*2438*2896
Heat Dissipation Capacity(kW) 1000 1000
Outlet Temperature @ 28℃ Wet Bulb Temperature 35℃ 35℃
Container Certification None China Classification Society Certification
Safety Certification North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, CSA C22.2 No. 14-18, ANSI/ISO 12100:2012
EU Standards: EN ISO 12100, EN 60204-1
North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, CSA C22.2 No. 14-18, ANSI/ISO 12100:2012
EU Standards: EN ISO 12100, EN 60204-1
Operating Power(kW) 14~28 14~28
Motor Rated Voltage and Frequency 415V±5% 60Hz(North America)
400V±5% 50Hz(EU,Middle East)
415V±5% 60Hz(North America)
400V±5% 50Hz(EU,Middle East)
Detailed Characteristics Value
Shipping Weight(T) 5 6
Operating Weight(T) 9 10
Connection Interface(Container) DN125(GB/T 9119-2010 PN16 DN125) DN125(GB/T 9119-2010 PN16 DN125)
Water Resupply Pipe Interface DN40(Internal thread) DN40(Internal thread)
Drain Pipe Interface DN65(Internal thread) DN65(Internal thread)
Noise Level @25℃, 16m 70dBA 70dBA
Water Consumption(m³/h) 1~1.5 1~1.5

 

 

 

 

About us--Marine King Miner                   click picture to view more

ANTMINER S19 Pro+ Hyd 198TH/S With ANTSPACE HK3 And DWT-T/DWT-C Dry-Wet Towers Liquid Cooling Suit 0

 

Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
+